Room actuator 230 V
Rail mounting device, 4 rail units
with manual electronic operation and LED status indicator
For projecting and commissioning the use of ETS 3.0d is recommended.
Only with this version or later versions the full functionality will be available.
ETS product family: Output
Product type: Binary output
Designated use
- Switching of electrical consumers AC 230 V with potential-free contacts
- Switching of electrically operated blinds, shutters, awnings and similar curtains
- Heating outputs: electronic outputs for switching electro-thermal valve drives
Product features
- Manual output control, provisional operation
- Feedback in manual control mode and in bus operation
- Scene function
- Disabling of individual outputs by hand or via the bus
Switching function
- Make-contact and break-contact operation
- Logic operation and forcing function
- Feedback function
- Central switching function with group feedback
- Time functions: ON-delay, OFF-delay, staircase lighting timer with early-warning function
Blind/shutter function
- Suitable for AC motors 230 V
- Direct control of blind/shutter position
- Direct control of slat position
- Checkback of running state, blind/shutter position and slat position
- Forced-control position from primary control
- Safety function: 3 independent wind alarms, rain alarm, frost alarm
- Sun protection function
Control of valve drives 230 V
- Switching or PWM operation
- Control of valve drives with working characteristics "normally open" or "normally closed“
- Overload and short-circuit protection
- Emergency operation in the event of bus failure for summer and winter
- Protection against jamming valves
- Forced-control position
Technical data | | |
| KNX supply: | 21 ... 32 V DC |
| Power consumption KNX: | max. 150 mW |
| Power supply mains: | AC 110 V ... 230 V ~, 50/60 Hz |
| Power loss: | max. 6 W |
| Ambient temperature: | -5 °C ... +45 °C |
| Storing temperature: | -25 °C ... +70 °C |
| Mounting width: | 72 mm (4 rail units) |
| Wiring, KNX: | bus connection block |
| Wiring, mains and outputs: | screw terminals |
| | single wire: | 0.5 ... 4 mm2 |
| | stranded without ferrule: | 0.5 ... 4 mm2 |
| | stranded with ferrule: | 0.5 ... 2.5 mm2 |
| Heating outputs | |
| Contact type: | semiconductor, ε |
| Switching voltage: | AC 230/240 V |
| Switching current: | 5 mA ... 50 mA |
| Starting current: | max. 1.5 A, 2 s |
| Number of drives per output: | max. 4 |
| Relay outputs | |
| Contact type: | potential-free make contact (µ contact) |
| Switching voltage: | AC 230/240 V |
| Breaking capacity AC1: | 16 A |
| Breaking capacity AC3: | 6 A |
| Breaking capacity fluorescent lamps: | 16 AX |
| Switching capacities per output | |
| ohmic load: | 3000 W |
| capacitive load: | 16 A, max. 140 µF |
| Motors: | 1380 VA |
| Lamp loads: | |
| | Incandescent lamps: | 3000 W |
| | HV halogen lamps: | 2500 W |
| | LV halogen lamps with: | |
| | – TRONIC transformer: | 1500 W |
| | – conventional transformer: | 1200 VA |
| | Fluorescent lamps: | |
| | – non-compensated: | 1000 W |
| | – parallel compensated: | 1160 W, max. 140 µF |
| | – lead-lag circuit: | 2300 W, max. 140 µF |